1.0 General
-
Acoustical Panel Enclosures
shall be insulated double-wall construction and shall be provided as indicated
on drawings by a recognized manufacturer with published standards of construction
and technical performance. The manufacturer shall have produced a standard
factory-fabricated panel system and components for at least 10 years. Performance
of the fabricated and installed system shall conform to all specifications
listed herein.
2.0 Materials
2.1 Acoustical Metal Panels
- All
panels and their components shall be pre-fabricated, sectional, all metal-clad,
modular and designed for easy and accurate field assembly. The panels and
components shall not be susceptible to damage due to extended exposure to
vibration, air temperature or humidity with the passage of time.
- Panel Construction
- All panels shall be (2)/(4)/(6) inches thick, as noted on drawings,
with a solid galvanized steel Type G90 exterior shell and a perforated/solid
galvanized steel type G90 interior shell. The panels shall be connected
together by means of a tongue and groove connection and held together
rigidly by the use of self-drilling sheet metal screws.
- The panel shell framing members and internal reinforcements shall be
welded, screwed and/or riveted together to form a metal-sheathed panel
of sufficient strength for maximum operating loads specified in the structural
performance section of these specifications.
- The solid exterior outer galvanized steel shell thickness shall be 18
ga. minimum and the interior perforated galvanized steel shell shall be
22-ga. minimum thick.
- Where perforated materials are indicated, all perforations shall be
3/32" dia. holes on 3/16" staggered centers and shall result
in an open area of no less than 23 percent.
- All panel internal and external reinforcing members shall be minimum
18 ga. galvanized steel.
- Each panel shall be filled with sound-absorbing materials that are inert,
mildew-resistant, verminproof, and incombustible.
- Panel Components and Installation
- All accessory trim items shall be of 18 ga. minimum galvanized steel
and shall be furnished in factory-standard lengths to be field cut to
specified dimensions. Location and quantity of sheet metal screws and
trim requirements shall be in accordance with the manufacturer’s
installation details.
- Base channel shall be installed on a level and structurally sound surface.
- All external panel connectors, trim items, accessories, base channel/panel
interfaces/base channel/floor interfaces, and other sections as noted
on the drawings shall be sealed with an acoustical sealant that shall
not harden and prevent disassembly in the future.
- Structural Performance
- Any special external panel loading conditions including wind, snow and
equipment shall be provided for as per specifications.
- Under the indicated loading conditions, the entire enclosure system
shall be self-supporting and/or will be supported as per the specifications.
The installer shall furnish and assemble all structural members in strict
accordance with drawings and manufacturer’s installation details.
- Under the above loading conditions, the assembled acoustical structure
shall not exhibit any panel joint deflection in excess of L/240, where
L is the unsupported span length of any panel section in the erected structure.
- Acoustical Performance
- The manufacturer shall provide certified testing data indicating sound
absorption and transmission loss characteristics of the panel assembly.
- Accessory Items
- Doors, windows, electrical systems, ventilating systems, accessory
components, etc., shall be provided in accordance with drawings.
- Manufacturer
- All materials shall be provided by Kinetics Noise Control, Inc. - Vibron
Products Group.