Spring Wire-Tie Ceiling Hanger

Request A Quote

Will the desired plenum space wind up covered with duct, pipe, and related MEP items packed in so closely that you can’t suspend ceiling isolation hangers close to the deck? Don’t limit your options for optimal ceiling isolation hangers. The Kinetics Muta hanger is an excellent choice when using wire to suspend the ceiling grid. With a full one-inch rated deflection spring in series with a rubber element, it is easy to resiliently support one or more layers of gypsum board.

Resources


Drawings | BIM


BIM OBJECT

ZIP

Typical Perimeter Condition

PDF

DWG

Isolated Ceiling Penetration

PDF

DWG

Muta and KSCH with Ductwork

PDF



Submittal Documents


Click on image to enlarge. Download multiple files by checking orange boxes next to desired files then click EXPORT.

System Components


RESILIENT INTERFACE (CPT)

SEALANT


Drawings


Submittal Drawing

Ceiling Hanger At Perimeter

Isolated Ceiling Penetration

Muta and KSCH with Ductwork


Additional Documents


DATA SHEET

Installation Guidelines

Selection Guidelines

SPECIFICATIONS

LEED

WARRANTY



Installation Guidelines


DOWNLOAD

IMPORTANT! PLEASE READ FIRST:
These suggested installation guidelines represent generally accepted procedures for successful installation of Kinetics Noise Control Muta Wire-Suspended Ceiling Hanger for ceiling system isolation. These suggestions may be followed, modified, or rejected by the owner, engineer, contractor, and/or their respective representative(s) since they, not Kinetics Noise Control, are responsible for planning and executing procedures appropriate to a specific application. Kinetics Noise Control reserves the right to alter these suggestions and encourages contact with the factory or its representatives to review any possible modification to these suggested guidelines prior to commencing installation.

      • 1. Installation of an isolated ceiling system that uses Kinetics Noise Control Muta Ceiling Hangers requires following materials (as specified by others and purchased separately):
          • A. 1-1/2" x 1/2", 16-gauge cold-rolled channel.
          • B. 7/8" 20- to 25-gauge drywall furring channel.
          • C. Appropriate wire (per local code).
          • D. Anchors for mounting wire into non-isolated ceiling substrate.
          • E. 1/2" or 5/8" thick gypsum board.
          • F. Appropriate tools and equipment for installation.

If submittal drawings have been prepared for the installation, review drawings for completeness and accuracy; otherwise, refer to Selection Guidelines for selecting ceiling hangers.

      • 2. Mark grid pattern on existing non-isolated ceiling using the following criteria:
          • A. Isolators installed at the perimeter must be located not more than 12" from the edge of the isolated ceiling; maintain at least a three-inch clearance from the perimeter.
          • B. Isolators may be located up to 48" along the perimeter of the isolated ceiling.
          • C. Isolators mounted mid-room (i.e., those isolators not at the perimeter) may be located up to 48" on center each way (o.c.e.w.); mid-room isolators should be spaced evenly in each direction.

Shop drawings, if provided, override general location guidelines provided above.

      • 3. Remove Muta Hangers from box. Confirm capacity of each isolator to ensure proper location in grid. If provided, shop drawings will identify location of specific hanger by capacity rating. After determining the direction the cold-roll channel will run (orientation is not important acoustically), locate the wire at the intersect points on the grid. Anchor wire to non-isolated ceiling using appropriate fastener and tie the loose end to the eyebolt that goes through the rubber element. Tie cold-rolled channel to the other (bottom) eyebolt. Position the cold-rolled channel to prevent contact at partition/wall/column or any other non-isolated structural component. Inter-connect ends of cold-rolled channel using appropriate practices for ceiling grid installation.
      • 4. Attach drywall furring channel to cold-rolled steel and inter-connect the ends of the furring channel using appropriate practices for ceiling grid installation. Furring channel cannot contact non-isolated structural components.
      • 5. After assembling the ceiling grid, check for levelness. By loosening or tightening the wire, the grid can be adjusted to level.
      • 6. Install CPT perimeter interface at partitions/walls, columns, and around any non-isolated building components to create a 3/8" wide resilient layer that ensures the isolated ceiling remains decoupled from the non-isolated structure. As the gypsum board is attached to the grid, the springs will compress (1/2” to 1-1/4” nominally depending on spring capacity) allowing the ceiling system to lower into final position. Position the CPT to account for this change to final elevation. Trimming the CPT may be required following installation of the gypsum board. If an alternate method for ensuring that the isolated ceiling remains decoupled is employed (e.g., using resilient backer rod), be sure to maintain a 3/8" gap from non-isolated structural components.
      • 7. Install the gypsum board using accepted practices for attaching to the grid system. Be certain to maintain a 3/8" gap between non-isolated structural components and the isolated ceiling to ensure that the gypsum board does not contact any non-isolated structural components. Do not allow gypsum board to rest on top edge of CPT; it should abut the perimeter isolation board. Do not allow the CPT to become compressed against the non-isolated structure. In some cases, additional adjustment of the gypsum board may be necessary to achieve levelness, consult factory for procedures.
      • 8. Trim CPT as required and caulk gap using a resilient, non-hardening caulk.


Design Guidelines


Selection Guidelines


DOWNLOAD

IMPORTANT! PLEASE READ FIRST:
These suggested selection guidelines represent generally accepted procedures for properly selecting Kinetics Noise Control Muta Wire-Suspended Ceiling Hanger for ceiling system isolation. These suggestions may be followed, modified, or rejected by the owner, engineer, contractor, and/or their respective representative(s) since they, not Kinetics Noise Control, are responsible for planning and executing procedures appropriate to a specific application. Kinetics Noise Control reserves the right to alter these suggestions and encourages contact with the factory or its representatives to review any possible modification to these suggested guidelines prior to commencing selection.

    • 1. Define ceiling area being isolated and sketch a layout showing the ceiling hanger locations per the following criteria (refer to layout diagram below):
        • A. Isolators installed at the perimeter must be located not more than 12" from the edge of the isolated ceiling; maintain at least a three-inch clearance from the perimeter.
        • B. Isolators may be located up to 48" along the perimeter of the isolated ceiling.
        • C. Isolators mounted mid-room (i.e., those isolators not at the perimeter) may be located up to 48" on center each way (o.c.e.w.).
        • D. Many room configurations will require non-conventional placement of isolation hangers to support the gypsum board ceiling (i.e., every isolated ceiling cannot be laid out in even rows in each direction). Consideration must be given to supporting the gypsum board ceiling adequately; this may require unique spacing arrangements to accommodate installation of the ceiling grid.
    • 2. Once spacing of the ceiling hangers is determined and sketched, three (3) general areas of the ceiling require load calculations: mid-room, along the perimeter, and in the corners. The total number of calculations required depends on how varied the spacing of the hangers is in each of these areas.
    • 3. Determine the total weight of the layers of gypsum wallboard and ceiling grid components being supported by the isolation hangers. The chart below is useful in determining common weights for materials used in isolated ceiling construction:
Building Material Weight (psf):
R11 (3-1/2" Fiberglass Batt) 0.50
1-1/2" CRC and 7/8" DWF 0.50
1/2" Gypsum Board (Type X) 2
5/8" Gypsum Board (Type X) 2.4
    • 4. Additional items such as lights or a lay-in tile ceiling may be suspended from the gypsum board/ceiling grid assembly. The weight of these items needs to be considered when determining the appropriate number/capacity of hangers required.
    • 5. Calculate load at each hanger location:
        • ______lbs./hanger = Total psf of ceiling materials x SF area carried by each hanger
        • Where, psf = pounds per square foot
        • SF = square feet
    • 6. Select appropriate hanger for each location from chart below. Designated model numbers indicate the load at which the isolator deflects one-inch (1") (nominal). Every hanger has at least a 50% overload capacity; it is possible to slightly exceed the maximum capacity shown in the chart below:
Model Spring Color Capacity Range (lbs.) Deflection Range (in.)
12 Silver 6-12 0.50-1.00
18 Yellow 9-18 0.50-1.00
24 Blue 12-24 0.50-1.00
30 Pink 15-30 0.50-1.00
37 White 19-37 0.50-1.00
50 Green 25-50 0.50-1.00
75 Black 38-75 0.50-1.00
100 Gray 50-100 0.50-1.00
150 Red 75-150 0.50-1.00
210 Brown 105-210 0.50-1.00
300 Purple 150-300 0.50-1.00
370 Orange 193-385 0.50-1.00

Using eyebolts (welded closed) at the top and bottom of the hanger body, installing contractors can suspend the hanger assembly anywhere in the plenum between the deck above and the grid below, easily avoiding duct and pipe. At least a 15-inch airspace forms between the concrete deck and gypsum board if all hangers are suspended at the same elevation. In other words, this is a hanger that allows for flexible installation in a crowded plenum space. Installing contractors familiar with wire-tying will be able to incorporate MUTA into the hanger grid system, ensuring the hanger system is installed plumb.

Features

  • Familiar wire-tie fittings allow maximum installation flexibility
  • Use with cold-rolled channel (CRC) or drywall grid systems
  • Spring capacities up to 370 pounds and one-inch rated deflection
  • A level ceiling is ensured due to MUTA’s twelve (12) different spring capacities