The noise source is an outdoor Air-Cooled Chiller. Noise is emanating into critical areas: screw compressors (on the bottom of the unit) generate mid/hi frequency noise; Up-blast fans (on the top) generate low frequency noise.
A common but inadequate attempt to control the noise is to wrap the compressors with massloaded vinyl jackets. This rarely solves the noise problem.
Three and four-sided Model STL, acoustical barrier wall systems, allowing sufficient space between barrier/chiller as well as equipment and access doors as required. Add on VAL acoustical louvered skirt for ventilation. Add on VAR acoustical louvered roof system to redirect noise from critical areas, achieving maximum noise reduction at a very low pressure drop. Systems can be located on grade or rooftop.
Download Kinetics Barrier Wall (Chiller) Systems Specifications
Select an image to open a larger view in new window.
Our knowledge and experience save time and money. Modular units ship knocked down for easy transport and quick field assembly. Product manufactured from galvanized steel or aluminum and can be factory powder-coated or field painted.
Sound Transmission Loss per ASTM E90
| Octave Band Number | 2 | 3 | 4 | 5 | 6 | 7 | STC |
|---|---|---|---|---|---|---|---|
| Center Frequency (Hz) | 125 | 250 | 500 | 1000 | 2000 | 4000 | --- |
| NOISEBLOCK™ (STL)-2" (18s/22p) | 17 | 23 | 34 | 47 | 55 | 57 | 37 |
| NOISEBLOCK™ (STL)-2" (18s/22s) | 17 | 29 | 45 | 55 | 58 | 58 | 41 |
| NOISEBLOCK™ (STL)-4" (18s/22p) | 21 | 28 | 39 | 48 | 56 | 58 | 40 |
| NOISEBLOCK™ (STL)-4" (18s/22s) | 21 | 34 | 52 | 58 | 60 | 60 | 44 |
| NOISEBLOCK™ (HTL)-4" (16s/22p) | 27 | 34 | 48 | 61 | 66 | 70 | 48 |
| NOISEBLOCK™ (HTL)-4" (16s/22s) | 27 | 39 | 59 | 68 | 67 | 72 | 52 |