Login: Rep ToolsOnline SilencersE-Business Portal
Your source for Noise, Acoustic, Vibration and Seismic control systems, 1-877-457-2695
Home > Vibration Isolation for HVAC Systems > Structural Steel Bases > Model SFB

KINETICS®

Structural Frame Bases

Model SFB

Structural Frame Base

Application

Kinetics Model SFB Structural Frame Bases are specifically designed and engineered to support mechanical equipment requiring a supplemental mounting frame.

Structural frame bases are used to support mechanical equipment and provide rigid platforms for attachment of vibration isolators, without allowing excessive differential movement between driving and driven members. The bases provide a means by which the equipment can be stabilized and motion reduced by lowering the equipment center of gravity.

Typical uses of Kinetics Model SFB structural frame bases, with Kinetics vibration isolators, include support and isolation of reciprocating chillers, close coupled pumps, vent sets, packaged air handling units, centrifugal fans, evaporative condensers, and similar types of equipment.

Features

Description

Kinetics Model SFB Welded Structural Frame Bases are individually engineered to support and add rigidity to a specific piece of mechanical equipment and to allow the use of selected vibration isolators. The bases provide a rigid frame to reduce motion on start-up and maintain belt or drive alignment. The bases are fabricated with channels, angles, or WF beams, and are complete with outboard heightsaving isolator brackets and prelocated equipment anchor bolts. Main steel members have section depths of 3" to 12" (76 mm to 305 mm), designed to be a minimum of 10% of the longest span between isolators.

Specifications

Standard Structural Members Flange Width Weight per ft.(m) Length/Width
Angle - 2" x 3" 51 mm x 76 mm 2" 51 mm 4.1 #/ft. 5.8 kg/m As Required
Angle - 3" x 4" 76 mm x 120 mm 3" 76 mm 5.8 #/ft. 8.2 kg/m
Angle - 3-1/2" x 6" 89 mm x 152 mm 3-1/2" 89 mm 7.9 #/ft. 11.2 kg/m
Channel - 4" 102 mm 1-5/8" 41 mm 5.4 #/ft. 7.6 kg/m As Required
Channel - 6" 152 mm 1-15/16" 49 mm 8.2 #/ft. 11.6 kg/m
Channel - 8" 203 mm 1-7/8" 48 mm 8.5 #/ft. 12.0 kg/m
WF Beam - 6" 152 mm 4" 102 mm 8.5 #/ft. 12.0 kg/m As Required
WF Beam - 8" 203 mm 4" 102 mm 10.0 #/ft. 14.1 kg/m
WF Beam - 10" 254 mm 4" 102 mm 11.5 #/ft. 16.3 kg/m
WF Beam - 12" 305 mm 4" 102 mm 14.0 #/ft. 19.8 kg/m

Bases shall be fabricated from structural beam sections with welded isolator brackets and prelocated anchor bolt holes, and shall be designed and supplied by the isolation materials manufacturer.

Section depth of each member shall be greater than 10% of the longest span between supporting isolators, or as shown on the drawings or indicated in the project documents. Isolator support brackets shall be welded to the structural beams as required to obtain the lowest mounting height for the supported equipment.

Lateral cross members shall be added to form a structurally integral, welded frame to provide a rigid, distortion-free frame to support and anchor separate equipment components or driving and driven members.

Structural frame bases shall be Model SFB, as manufactured by Kinetics Noise Control, Inc.

Model SFB Structural Frame Base