KINETICS® FHS & FHSLSeismic Control Spring Isolator

FHS/FHSL Seismic Control Spring Isolators are used to reduce the transmission of noise and vibration into supporting structures from supported mechanical equipment. FHS/FHSL are recommended for noise and vibration isolation for mechanical equipment located near critically quiet areas when there is a possibility that the equipment to be isolated will be subjected to the external forces associated with an earthquake.

Project Focus

The Universities at Shady Grove Biomedical Sciences and Engineering Building

 

Request A Quote

BIM OBJECTS


FHS ISOLATOR W/ OPTIONAL OVERSIZED BASEPLATES

PDF

DWG

Features

  • All-directional restraint with vertical limit stops.
  • Field-interchangeable spring coils.
  • Galvanized housing and polyester powder coated coils.
  • Constant free height & operating height.
  • Equipment motion limited to 0.2" (5 mm) in all directions, at the isolator.
  • California Pre-Approval Number R-0433

Application

Kinetics FHS and FHSL seismic control spring isolators are recommended for noise and vibration isolation for mechanical equipment located near critically quiet areas when there is a possibility that the equipment to be isolated will be subjected to the external forces associated with an earthquake. FHS/FHSL isolators are used to reduce the transmission of noise and vibration into supporting structures from supported mechanical equipment. Motion during an earthquake which would otherwise displace life support and emergency equipment is limited, and the equipment remains in position. Anchorage of FHS/FHSL isolators should be designed by a professional engineer and isolators selected based on calculated anticipated forces.


Description

FHS/FHSL seismic control spring isolators meet the specifications for Kinetics FDS isolators. Additionally, FHS isolators include a steel housing assembly to limit both lateral and vertical movement of the supported equipment during an earthquake without degrading the vibration isolation of the spring during normal equipment operating conditions.

FHS/FHSL isolators incorporate a steel housing which encloses a neoprene snubber. Depending on the load and seismic code, an optional steel load spreader plate may be applied to distribute the load among concrete anchors. A neoprene pad fitted in series with the spring is provided. Equipment attachment is by way of a bolt screwed downward through the equipment foot. Equipment motion is limited to approximately 0.2" (5 mm) in any direction, at the isolator. In conformance with all current building code standards, the restraining system is designed to withstand a minimum 1.0 g acceleration force. Removal of the isolator for servicing is quick and easy as the isolator is not fitted with a protruding stud.

Specifications

Spring isolators shall be seismic control restrained spring isolators, incorporating a single vibration isolator, having all the characteristics of Kinetics FDS open spring isolators as previously specified. Springs shall be restrained using a housing engineered to limit both lateral and vertical movement of the supported equipment during an earthquake without degrading the vibration isolation of the spring during normal equipment operating conditions.

Vibration isolators shall incorporate a steel housing and snubbing grommet system designed to limit motion to approximately 0.2" (5 mm) in any direction and to prevent any direct metal-to-metal contact between the supported member and the fixed housing. The restraining system shall be designed to withstand a force equivalent to 1.0 g in any lateral or vertical direction without yield or failure. Where the capacity of the anchorage hardware in concrete is inadequate for the required seismic loadings, an adapter plate to allow the addition of more or larger anchors will be fitted to fulfill these requirements. In addition to the primary isolation spring, the load path will include a minimum 0.25 inch (6mm) thick neoprene pad.

To facilitate servicing, the isolator will be designed in such a way that it can be removed without the requirement to lift or otherwise disturb the supported equipment.

Spring isolators shall be model FHS and FHSL as manufactured by Kinetics Noise Control.