Application:
For use when wall isolation is desired for wood-and steel-frame studwall
construction, Model KWSB2 Anti-Buckling Brace will eliminate the "give" felt
when leaning on a wall that is acoustically isolated. Model KWSB2 is especially
useful when construction requires that the vertical framing channels/studs
be split. The Model KWSB2 can be implemented in many construction situations,
as it is seismically rated, and allows for a narrow airspace between two walls.
Benefits:
- 10-ga galvanized steel bracket
- Standoff not more than 1-3/4" between studs
- Capable of withstanding a seismic generated
force of 50 lbs.
- 1/4" thru hole for easy installation
Specifications:
Part 1.00 - General
1.01 Work
Included
A. Furnish all labor, materials, tools and equipment, and perform all operations
necessary for the installation of anti-buckling, resilient partition braces
in the construction of an isolated partition.
1.02 System
Description
A. Isolated partitions, where shown on drawings, shall be decoupled along
the studs using partition isolation braces that prevent buckling. Partition
isolation braces shall be used in conjunction with other isolation components
or systems, as required, to enable construction of an isolated partition and
ensure reduced sound transmission.
1.03 Quality
Assurance
A. Resilient partition braces shall be designed and fabricated at facilities
of a nationally recognized manufacturer having a minimum of five years experience
in furnishing similar materials.
Part 2.00 - Products
2.01 Materials
A. The resilient isolation components specified herein shall be designed
and manufactured by Kinetics Noise Control, Inc. Dublin, Ohio.
B. Isolated partitions shall be constructed using Kinetics Model KWSB2 Anti-Buckling
Resilient Partition Braces. Resilient partition braces shall be capable of
withstanding a seismic generated force of fifty (50) pounds.
C. Resilient partition braces shall be constructed using galvanized steel
brackets interlocked with a neoprene noise and vibration insert. Resilient
partition braces shall contain two 1/4" diameter thru-holes to permit use of
fasteners to attach braces to studs.
Part 3.00 - Execution
3.01 Installation
A. The installation of all resilient isolation materials specified herein,
including those installed under other sections of the specifications, shall
be in accordance with procedures submitted by the isolation material manufacturer,
and approved by the Architect.